Sinamics Link Send Telegram Word Pzd / Send Link Word - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

p8871[0...15]

SINAMICS Link send telegram word PZD / Send link word

CU_DC (PROFINET
Can be changed: T
CBE20), CU_DC_R
Data type: Unsigned16
(PROFINET CBE20),
P-Group: Communications
CU_DC_R_S
Not for motor type: -
(PROFINET CBE20),
CU_DC_S
Min
(PROFINET CBE20),
0
DC_CTRL (PROFINET
CBE20), DC_CTRL_R
(PROFINET CBE20),
DC_CTRL_R_S
(PROFINET CBE20),
DC_CTRL_S
(PROFINET CBE20),
TM150 (PROFINET
CBE20), TM15DI_DO
(PROFINET CBE20),
TM31 (PROFINET
CBE20)
Description:
Assigns a PZD to a telegram word in the SINAMICS Link send telegram.
For p8839[0] = 2 (COMM BOARD via interface 1), the following applies:
- p8871[index] assigns PZD p2051[index].
For p8839[1] = 2 (COMM BOARD via interface 2), the following applies:
- p8871[index] assigns PZD p8851[index].
Index:
[0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
Dependency:
Refer to: p2051, p8851
Note:
Value range:
0: Not used
1 ... 16: Send telegram word
A specific telegram word send may only be used once within a single device.
A change only becomes effective after POWER ON, reset, project download or p8842 = 1.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
16
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
331