2 Parameters
2.2 List of parameters
r50047[0...31]

Faults additional information / Fault add info

DC_CTRL
Can be changed: -
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Displays more detailed information about faults which have occurred with numbers 60000 and higher.
[0] = Fault value
[1] = Additional information about the most recent fault which occurred (see corresponding fault)
...
[30] = Additional information about the most recent fault which occurred (see corresponding fault)
[31] = Fault number
p50051

Optimization run selection / Opt run sel

DC_CTRL
Can be changed: C2(1), T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Setting to select the optimization run for the next ON command.
Value:
0:
23:
24:
25:
26:
27:
28:
29:
30:
Notice:
If value = 30:
The CCP optimization run does not require a switch-on command and is directly started when selecting the value.
Note:
Only a value of 0 can be set at the right-hand CUD.
A value not equal to 0 can only be set in the operating states o7.0 and o7.1 if an optimization run is presently not
active.
If value = 0:
No optimization run has been selected.
If value = 23:
Optimization run for pre-control and the current controller for the armature converter (for inductive loads).
If value = 24:
Optimization run for pre-control and the current controller for the field converter.
If value = 25:
Optimization run for pre-control and the current controller for the armature converter.
If value = 26:
Optimization run for the speed controller and moment of inertia.
If value = 27:
Optimization run for field weakening.
If value = 28:
Optimization run for friction compensation.
If value = 29:
Optimization run for speed controllers and moment of inertia for drives that are capable of oscillation.
If value = 30:
Optimization run for CCP (Converter Commutation Protector).
384
No optimization run
Armature current control (for inductive loads)
Closed-loop field current control
Closed-loop armature current control
Closed-loop speed control and moment of inertia
Field weakening control
Friction compensation
Torsion optimization
CCP (Converter Commutation Protector)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
30
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 1
Func. diagram: 2651
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 1
Func. diagram: 2660
Unit selection: -
Expert list: 1
Factory setting
0