Fault Cases Counter / Fault Cases Qty - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Dependency:
Refer to: r0945, r0947, r0949, r2109, r2114, r2130, r2133, r2136, r3115, r3120, r3122
Notice:
The time comprises r2130 (days) and r0948 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
r0949[0...63]
Fault value / Fault value
CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Integer32
CU_DC_S, DC_CTRL,
P-Group: Messages
DC_CTRL_R,
Not for motor type: -
DC_CTRL_R_S,
DC_CTRL_S
Min
-
Description:
Displays additional information about the fault that occurred (as integer number).
Dependency:
Refer to: r0945, r0947, r0948, r2109, r2130, r2133, r2136, r3115, r3120, r3122
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
r0949[0...63]
Fault value / Fault value
TM150, TM15DI_DO,
Can be changed: -
TM31
Data type: Integer32
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays additional information about the fault that occurred (as integer number).
Dependency:
Refer to: r0945, r0947, r0948, r2109, r2130, r2133, r2136, r3115, r3120, r3122
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
p0952

Fault cases counter / Fault cases qty

CU_DC, CU_DC_R,
Can be changed: U, T
CU_DC_R_S,
Data type: Unsigned16
CU_DC_S, DC_CTRL,
P-Group: Messages
DC_CTRL_R,
Not for motor type: -
DC_CTRL_R_S,
DC_CTRL_S
Min
0
Description:
Number of fault situations that have occurred since the last reset.
Dependency:
The fault buffer is deleted (cleared) by setting p0952 to 0.
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136
p0952
Fault cases counter / Fault cases qty
TM150, TM15DI_DO,
Can be changed: U, T
TM31
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
0
Description:
Number of fault situations that have occurred since the last reset.
Dependency:
The fault buffer is deleted (cleared) by setting p0952 to 0.
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65535
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8060
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8050, 8060
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8060
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 6700, 8060
Unit selection: -
Expert list: 1
Factory setting
0
109