2 Parameters
2.2 List of parameters
3:
4:
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency:
Refer to: p4077, p4078, p4079, p4080
Note:
When changing p4076, the parameters of the scaling characteristic (p4077, p4078, p4079, p4080) are overwritten
with the following default values:
For p4076 = 0, 3, p4077 is set to 0.0 %, p4078 to 0.0 mA, p4079 to 100.0 % and p4080 to 20.0 mA.
For p4076 = 1, 4, p4077 is set to 0.0 %, p4078 to 0.0 V, p4079 to 100.0 % and p4080 to 10.0 V.
For p4076 = 2, p4077 is set to 0.0 %, p4078 to 4.0 mA, p4079 to 100.0 % and p4080 to 20.0 mA.
p4077[0...1]

TM31 analog outputs characteristic value x1 / TM31 AO char x1

TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog outputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency:
Refer to: p4076
Notice:
This parameter is automatically overwritten when changing p4076 (type of analog outputs).
Note:
The parameters for the characteristic do not have a limiting effect.
p4078[0...1]

TM31 analog outputs characteristic value y1 / TM31 AO char y1

TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-20.000 [V]
Description:
Sets the scaling characteristic for the analog outputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 1st value pair of the
characteristic.
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency:
The unit of this parameter (V or mA) depends on the analog output type.
Refer to: p4076
Notice:
This parameter is automatically overwritten when changing p4076 (type of analog outputs).
Note:
The parameters for the characteristic do not have a limiting effect.
p4079[0...1]

TM31 analog outputs characteristic value x2 / TM31 AO char x2

TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog outputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog outputs is defined using 2 points.
230
Current output (-20 mA ... +20 mA)
Voltage output (-10 V ... +10 V)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000.00 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
20.000 [V]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000.00 [%]
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 9572
Unit selection: -
Expert list: 1
Factory setting
0.00 [%]
Access level: 2
Func. diagram: 9572
Unit selection: -
Expert list: 1
Factory setting
0.000 [V]
Access level: 2
Func. diagram: 9572
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]