2 Parameters
2.2 List of parameters
p8841[0...239]

COMM BOARD send configuration data / CB s config_dat

CU_DC (PROFINET
Can be changed: U, T
CBE20), CU_DC_R
Data type: Unsigned16
(PROFINET CBE20),
P-Group: Communications
CU_DC_R_S
Not for motor type: -
(PROFINET CBE20),
CU_DC_S
Min
(PROFINET CBE20)
0
Description:
Sets the send configuration data for the COMM BOARD.
The setting is activated with p8842.
Dependency:
Refer to: p8842
Note:
The configuration data are specific to the inserted COMM BOARD.
For CBE20, the configuration data are not relevant.
p8842

Activate COMM BOARD send configuration / CB s config act

CU_DC (PROFINET
Can be changed: U, T
CBE20), CU_DC_R
Data type: Unsigned16
(PROFINET CBE20),
P-Group: Communications
CU_DC_R_S
Not for motor type: -
(PROFINET CBE20),
CU_DC_S
Min
(PROFINET CBE20)
0
Description:
Activate a modified send configuration for COMM BOARD.
With p8842 = 1, the values in p8841 are transferred to the COMM BOARD and activated. After this, p8842 is
automatically set to zero.
Dependency:
Refer to: p8841
Note:
For CBE20, certain SINAMICS parameters are newly evaluated and activated. An existing, cyclic bus connection is
interrupted.
r8843.0...2

BO: IF2 PZD state / IF2 PZD state

CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Unsigned8
CU_DC_S
P-Group: Communications
Not for motor type: -
Min
-
Description:
Displays the PROFIdrive PZD state.
Bit field:
Bit
00
02
Dependency:
Refer to: p2044
Note:
When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
p8844

IF2 fault delay / IF2 F delay

DC_CTRL,
Can be changed: U, T
DC_CTRL_R,
Data type: FloatingPoint32
DC_CTRL_R_S,
P-Group: Communications
DC_CTRL_S
Not for motor type: -
Min
0 [s]
Description:
Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
Dependency:
Refer to: r2043
318
Signal name
Setpoint failure
Fieldbus oper
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100 [s]
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
0 [s]