Closed-Loop Armature Current Control P Gain / Ia Ctr Kp; Closed-Loop Armature Current Control Integral Time / Ia Ctr Tn; Current Limitation Setpoint Integrator Selection / I_Set Integ Sel - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Note:
If value = 0:
The integral component of the armature current controller is kept constantly at zero (i.e. the armature current
controller functions solely as a proportional controller).
p50155[0...n]

Closed-loop armature current control P gain / Ia ctr Kp

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.01
Description:
Sets the P gain of the armature current controller.
Dependency:
Refer to: p50175
Note:
The parameter is set automatically during the optimization run for pre-control and the current controller for the
armature converter (p50051 = 25).
The P gain (Kp) for the armature current controller is calculated as follows:
Kp = p50155 x |p50175|
p50156[0...n]

Closed-loop armature current control integral time / Ia ctr Tn

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.001 [s]
Description:
Sets the integral time of the armature current controller.
Dependency:
Refer to: p50176
Note:
The parameter is set automatically during the optimization run for pre-control and the current controller for the
armature converter (p50051 = 25).
The integral time (Tn) for the armature current controller is calculated as follows:
Tn = p50156 x |p50176|
p50157[0...n]

Current limitation setpoint integrator selection / I_set integ sel

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Selection of the current setpoint integrator.
Value:
0:
1:
Note:
If value = 0:
The integrator is only effective after a change in torque direction (only functions as a ramp-function generator for the
current setpoint until the first time the output reaches the setpoint at the integrator input after a change in torque
direction).
If value = 1:
The integrator is always effective (functions as a ramp-function generator for the current setpoint).
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Reduced gearbox stressing
Current setpoint integrator
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
200.00
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10.000 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 6855
Unit selection: -
Expert list: 1
Factory setting
0.10
Access level: 2
Func. diagram: 6855
Unit selection: -
Expert list: 1
Factory setting
0.200 [s]
Access level: 2
Func. diagram: 6845
Unit selection: -
Expert list: 1
Factory setting
0
411