Rfg Tracking Enable / Rfg Track Ena; Rfg Setting Value Selection / Rfg Set Val Sel; Rfg Setpoint Enable Delay Time / Rfg Set_Ena I_Del - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Bit field:
Bit
00
01
02
03
04
05
07
15
p50317[0...n]

RFG tracking enable / RFG track ena

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the enable for ramp-function generator tracking.
Value:
0:
1:
Dependency:
RFG tracking has to be controlled by setting a 1 signal at binector input p50647.
Refer to: p50647
p50318[0...n]

RFG setting value selection / RFG set val sel

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Selection of the setting value for the ramp-function generator output for OFF1.
Value:
0:
1:
2:
Recommendation:
During "shutdown", limiting is not applied to the ramp-function generator output. As limiting the ramp-function
generator output during "shutdown" does not generate a temporary increase in speed, p50318 should be set to 1 or
2.
Dependency:
Refer to: p50650
Note:
If p50318 = 0:
The ramp-function generator output is not set.
If p50318 = 1:
The value supplied via connector input p50650[0] is applied as the setting value.
If p50318 = 2:
The value supplied via connector input p50650[1] is applied as the setting value.
p50319[0...n]

RFG setpoint enable delay time / RFG set_ena i_del

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [s]
Description:
Sets the delay time for enabling the setpoint on the ramp-function generator.
In the case of a setpoint enable, the setpoint is not injected on the ramp-function generator until this time has
elapsed.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Signal name
RFG enable
RFG start
Setpoint enable & OFF1
Set ramp-function generator
Track ramp-function generator
Bypass ramp-function generator
Ramp-down
Ramp-up
Inhibit
Enable
Ramp-function generator output not set
Set RFG output to setting value 1
Set RFG output to setting value 2
1 signal
ON
ON
ON
ON
ON
ON
ON
ON
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10.00 [s]
2 Parameters
2.2 List of parameters
0 signal
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Access level: 2
Func. diagram: 3152
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 3152
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 3151
Unit selection: -
Expert list: 1
Factory setting
0.00 [s]
FP
3152
3152
3152
3152
3152
3152
3152
3152
441