Messages For Overspeed Threshold Positive Direction Of Rotation; Messages For Overspeed Threshold Negative Direction Of Rotation; Messages For Setpoint/Actual Value Deviation 1 Threshold - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

p50380[0...n]
Messages for overspeed threshold positive direction of rotation / Msg n_over pos
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.0 [%]
Description:
Sets the threshold for the maximum speed in positive direction of rotation.
Dependency:
Refer to: p50381, p50595, r53025
Refer to: F60038
Note:
The "Overspeed" message is available as follows:
- F60038
- r53025.10 (not inverted)
- r53025.11 (inverted)
p50381[0...n]
Messages for overspeed threshold negative direction of rotation / Msg n_over neg
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-200.0 [%]
Description:
Sets the threshold for the maximum speed in negative direction of rotation.
Dependency:
Refer to: p50380, p50595, r53025
Refer to: F60038
Note:
The "Overspeed" message is available as follows:
- F60038
- r53025.10 (not inverted)
- r53025.11 (inverted)
p50388[0...n]
Messages for setpoint/actual value deviation 1 threshold / Set/act 1 thresh
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [%]
Description:
Sets the threshold for the "Setpoint/actual value deviation 1 reached" message.
Dependency:
Refer to: p50389, p50390, p50590, p50591, r53025
Refer to: F60031
Note:
The "Setpoint/actual value deviation 1 reached" message is available as follows:
- F60031
- r53025.0 (not inverted)
- r53025.1 (inverted)
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
200.0 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
0.0 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
200.00 [%]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8025
Unit selection: -
Expert list: 1
Factory setting
120.0 [%]
Access level: 2
Func. diagram: 8025
Unit selection: -
Expert list: 1
Factory setting
-120.0 [%]
Access level: 2
Func. diagram: 8020
Unit selection: -
Expert list: 1
Factory setting
3.00 [%]
449

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents