2 Parameters
2.2 List of parameters
p50430[0...7]
BI: Fixed setpoint signal source for connector selection / Fix set conn sig s
DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the selection of the connectors (p50431[0 to 7]).
Dependency:
Refer to: p50431, p50432, p50680, p50681, r52204, r52209, r52210, r53170
p50431[0...7]

CI: Signal source for fixed setpoint / Fix set sig s

DC_CTRL
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal sources for generating the fixed setpoint (CO: r52204).
Dependency:
Refer to: p50430, p50432, p50680, p50681, r52204, r52209, r52210, r53170
p50432[0...7]

Fixed setpoint bypass ramp-function generator / Fix set bypass RFG

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Setting to enable or disable the impact of the individual fixed setpoints when generating signal r53170.10, "Bypass
ramp-function generator".
Value:
0:
1:
Dependency:
Refer to: r53170
Note:
[0] = Enable bypassing of ramp-function generator at fixed setpoint 0
...
[7] = Enable bypassing of ramp-function generator at fixed setpoint 7
p50433[0...n]

CI: Signal source for default setpoint / Def set sig s

DC_CTRL
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the default setpoint.
458
Inhibit
Enable
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: PERCENT
Max
-
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 3115
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 3115
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 3115
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 3113
Unit selection: -
Expert list: 1
Factory setting
52011[0]
SINAMICS DCM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents