4 Faults and alarms
4.2 List of faults and alarms
F01107

CU: Save to memory card unsuccessful

Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A data save in the non-volatile memory was not able to be successfully carried out.
- non-volatile memory is defective.
- insufficient space in the non-volatile memory.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- try to save again.
- replace the memory card or Control Unit.
F01110

CU: More than one SINAMICS G on one Control Unit

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
TM150, TM15DI_DO, TM31
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
More than one SINAMICS G type power unit is being operated from the Control Unit.
Fault value (r0949, interpret decimal):
Number of the second drive with a SINAMICS G type power unit.
Remedy:
Only one SINAMICS G drive type is permitted.
F01111

CU: Mixed operation of drive units illegal

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Illegal operation of various drive units on one Control Unit:
- SINAMICS S together with SINAMICS G
- SINAMICS S together with SINAMICS S Value or Combi
Fault value (r0949, interpret decimal):
Number of the first drive object with a different power unit type.
Remedy:
Only power units of one particular drive type may be operated with one Control Unit.
F01112

CU: Power unit not permissible

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The connected power unit cannot be used together with this Control Unit.
Fault value (r0949, interpret decimal):
1: Power unit is not supported (e.g. PM240).
2: DC/AC power unit connected to CU310 not permissible.
3: Power unit (S120M) not permitted for vector control.
Remedy:
Replace the power unit that is not permissible by a component that is permissible.
888
List Manual (LH8), 02/2015, 6RX1800-0ED76
SINAMICS DCM