Technology Controller Actual Value Function / Tec_Ctr Actval Fct; Co: Technology Controller Actual Value Scaled / Tech_Ctrl Act Scal - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Note:
For 100%, the actual value is not changed.
p2270

Technology controller actual value function / Tec_ctr ActVal fct

DC_CTRL (Tech_ctrl),
Can be changed: U, T
DC_CTRL_R
Data type: Integer16
(Tech_ctrl),
P-Group: Technology
DC_CTRL_R_S
Not for motor type: -
(Tech_ctrl),
DC_CTRL_S
Min
(Tech_ctrl)
0
Description:
Setting to use an arithmetic function for the actual value signal of the technology controller.
Value:
0:
1:
2:
3:
Dependency:
Refer to: p2264, p2265, p2267, p2268, p2269, p2271
p2271
Technology controller actual value inversion (sensor type) / Tech_ctrl act inv
DC_CTRL (Tech_ctrl),
Can be changed: T
DC_CTRL_R
Data type: Integer16
(Tech_ctrl),
P-Group: Technology
DC_CTRL_R_S
Not for motor type: -
(Tech_ctrl),
DC_CTRL_S
Min
(Tech_ctrl)
0
Description:
Setting to invert the actual value signal of the technology controller.
The inversion depends on the sensor type for the actual value signal.
Value:
0:
1:
Caution:
If the actual value inversion is incorrectly selected, then the closed-loop control with the technology controller can
become unstable and can oscillate!
Note:
The correct setting can be determined as follows:
- inhibit the technology controller (p2200 = 0).
- increase the motor speed and in so doing, measure the actual value signal of the technology controller.
--> If the actual value increases as the motor speed increases, then p2271 should be set to 0 (no inversion).
--> If the actual value decreases as the motor speed increases, then p2271 should be set to 1 (the actual value signal
is inverted).
r2272

CO: Technology controller actual value scaled / Tech_ctrl act scal

DC_CTRL (Tech_ctrl),
Can be changed: -
DC_CTRL_R
Data type: FloatingPoint32
(Tech_ctrl),
P-Group: Technology
DC_CTRL_R_S
Not for motor type: -
(Tech_ctrl),
DC_CTRL_S
Min
(Tech_ctrl)
- [%]
Description:
Display and connector output for the scaled actual value signal of the technology controller.
Dependency:
Refer to: p2264, p2265, r2266, p2267, p2268, p2269, p2270, p2271
186
No function
Root function (root from x)
Square function (x * x)
Cube function (x * x * x)
No inversion
Inversion actual value signal
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: 9_1
Scaling: PERCENT
Max
- [%]
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 7958
Unit selection: p0595
Expert list: 1
Factory setting
- [%]
SINAMICS DCM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents