Armature Rated Direct Current / Arm I_Rated; Load Voltage At Armature Rated Current / V_Load Ia_Rated; Current Transformer Configuration / I_Transf Config; Power Unit Type / Pu Typ - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p51822

Armature rated direct current / Arm I_rated

DC_CTRL
Can be changed: T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.1 [A]
Description:
Sets the rated direct current for the armature.
The output direct current supported by the power unit in continuous operation should be set in this parameter.
Note:
The parameter is only effective on the Control Module.
p51823

Load voltage at armature rated current / V_load Ia_rated

DC_CTRL
Can be changed: T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.1000 [V]
Description:
Sets the load voltage resulting from the following calculation formula:
V_load = R_load * tr * Id
V_load: The load voltage to be set in this parameter
R_load: The load resistance (default 10 ohm)
r: Transformation ratio of the current transformer (I2 / I1)
Id: Output direct current according to parameter p51822
Note:
The parameter is only effective on the Control Module.
p51824

Current transformer configuration / I_transf config

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
1
Description:
Sets the configuration for the current transformer for current actual value sensing.
Value:
1:
2:
3:
4:
5:
Note:
The parameter is only effective on the Control Module.
p51825

Power unit type / PU typ

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
2
Description:
Sets the power unit type.
Value:
2:
4:
Note:
The parameter is only effective on the Control Module.
552
Current transformer in phase U and V
Current transformer in phase U and W
Current transformer in phase V and W
External current transformer connected in V circuit
Bipolar current actual value signal (external shunt)
2-quadrant power unit
4-quadrant power unit
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
20000.0 [A]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1.2000 [V]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
5
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
4
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 6965
Unit selection: -
Expert list: 1
Factory setting
0.1 [A]
Access level: 2
Func. diagram: 6850, 6965
Unit selection: -
Expert list: 1
Factory setting
1.0000 [V]
Access level: 2
Func. diagram: 6850, 6965
Unit selection: -
Expert list: 1
Factory setting
2
Access level: 2
Func. diagram: 6965
Unit selection: -
Expert list: 1
Factory setting
2
SINAMICS DCM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents