2.2 List of parameters
p4110[0...11]

TM150 wire resistance value / TM150 R_wire value

TM150
Can be changed: T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [ohm]
Description:
Sets and displays the wire resistance for Terminal Module 150 (TM150).
The value is used for the automatic conductor calibration.
The value is automatically set by starting the wire resistance measurement (p4109[0...11]) of the corresponding
channel.
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency:
Refer to: p4109
Notice:
Wire resistance measurement is only possible for 1x2 or 2x2 wire evaluation (p4108[0...5] = 0, 1).
Note:
Automatic conductor calibration is deactivated using p4110[0...11] = 0.
p4111[0...2]

TM150 group channel assignment / TM150 grp channel

TM150
Can be changed: T
Data type: Unsigned16
P-Group: -
Not for motor type: -
Min
-
Description:
Assigns the temperature channels to groups for the Terminal Module 150 (TM150)
For each group, the following calculated values are provided from the temperature actual values (r4105[0...11]):
- Maximum value (r4112[0...2])
- Minimum value (r4113[0...2])
- average value (r4114[0...2])
Index:
[0] = Group 0
[1] = Group 1
[2] = Group 2
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
Dependency:
Refer to: r4105, r4112, r4113, r4114
246
Signal name
Temperature channel 0
Temperature channel 1
Temperature channel 2
Temperature channel 3
Temperature channel 4
Temperature channel 5
Temperature channel 6
Temperature channel 7
Temperature channel 8
Temperature channel 9
Temperature channel 10
Temperature channel 11
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3000.00 [ohm]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 1
Func. diagram: 9626, 9627
Unit selection: -
Expert list: 1
Factory setting
0.00 [ohm]
Access level: 1
Func. diagram: 9625
Unit selection: -
Expert list: 1
Factory setting
0000 0000 0000 0000 bin
0 signal
No
No
No
No
No
No
No
No
No
No
No
No