Topology: Component Number Missing; Firmware Of The Drive-Cliq Component Being Updated; Topology: Component Must Not Be Present - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

F01305

Topology: Component number missing

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The component number from the topology was not parameterized (p0121 (for power unit, refer to p0107), p0131 (for
servo/vector drives, refer to p0107), p0141, p0151, p0161).
Fault value (r0949, interpret decimal):
Data set number.
Note:
The fault also occurs if encoders have been configured (p0187 to p0189) but no component numbers exist for them.
In this case, the fault value includes the drive data set number plus 100 * encoder number (e.g. 3xx, if a component
number was not entered in p0141 for encoder 3 (p0189)).
See also: p0121 (Power unit component number), p0141 (Encoder interface (Sensor Module) component number),
p0142 (Encoder component number), p0151 (Terminal Module component number), p0187 (Encoder 1 encoder data
set number), p0188 (Encoder 2 encoder data set number)
Remedy:
- enter missing component number.
- if required, remove the component and restart commissioning.
See also: p0121 (Power unit component number), p0141 (Encoder interface (Sensor Module) component number),
p0142 (Encoder component number), p0151 (Terminal Module component number), p0187 (Encoder 1 encoder data
set number), p0188 (Encoder 2 encoder data set number)
A01306

Firmware of the DRIVE-CLiQ component being updated

Message value:
%1
Message class:
General drive fault (19)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
Firmware update is active for at least one DRIVE-CLiQ component.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Remedy:
Not necessary.
This alarm automatically disappears after the firmware has been updated.
A01314

Topology: Component must not be present

Message value:
%1, to %2: %3, connection: %4
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
For a component, "de-activate and not present" is set but this component is still in the topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
aa = component number
bb = component class of the component
cc = connection number
Note:
Component class and connection number are described in F01375.
Remedy:
- remove the corresponding component.
- change the setting "de-activate and not present".
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
See also: p0105 (Activate/de-activate drive object), p0125 (Activate/de-activate power unit components), p0145
(Activate/de-activate encoder interface)
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms
895