2 Parameters
2.2 List of parameters
r50000

Operating display / Op_display

DC_CTRL
Can be changed: -
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
o0.0 No torque direction switched on
o0.1 Torque direction I switched on
o0.2 Torque direction II switched on
o0.9 Wait for enable from master
o1.0 Wait time for brake opening time running
o1.1 Wait for operating enable at terminal 13
o1.2 Wait for operating enable (signal source acc. to p0852)
o1.3 Wait time after withdrawing a jog command running
o1.4 Wait for field reversal to be implemented or for "Braking by field reversal" to be withdrawn
o1.5 Wait for operating enable from the optimization run
o1.6 Wait for withdrawal of the immediate pulse inhibit (signal source acc. to p50177)
o1.7 Wait until SINAMICS DCMs connected in parallel are in status o0
o1.8 Wait until the power unit topology has been switched over
o2.0 Wait for setpoint |r52193| > p50091[1]
o3.0 Wait for the thyristor check to be completed
o3.1 Wait for the line symmetry check to be completed
o3.2 Wait for a DC contactor to pick up
o3.3 Wait for the feedback signal, "line contactor" (signal source acc. to p50691)
o4.0 Wait for voltage at power connections 1U1, 1V1, 1W1
o4.1 Wait for fuse monitoring to signal OK
o4.5 Wait for pre-charging of the CCP's chopper capacitors to be completed
o5.0 Wait until the field current actual value r52265 is > p50396 and until "I_field ext > If_min" (see p50265)
o5.1 Wait for voltage at power connections 3U1, 3W1
Note:
A specific time, which can be set in p50089, represents the maximum wait time in states o4 and o5 combined. If, after
this time, the relevant conditions have still not been met, the corresponding error message will be triggered.
o6.0 Wait for the auxiliaries to power up (wait time p50093)
o6.1 Wait for a setpoint <= p50091[0] at the RFG input (p520193)
o7.0 Wait for power-on via terminal 12
o7.1 Wait for power-on (signal source according to p0840)
o7.2 Wait for the "Braking by field reversal" command to be withdrawn
o7.3 Wait for parallel master to power up
o7.4 Optimization run executes pre-work/post-work
o7.5 Wait until the SINAMICS DCM devices connected in parallel are ready to be switched on
o7.6 Wait for "Load MLFB" to be completed (carried out by manufacturer prior to delivery)
o8.0 Wait for closing lockout to be acknowledged
o8.1 Simulation mode active (see p51840)
o9.1 Quick stop (OFF3) (signal source acc. to p0848) present
o9.2 Quick stop (OFF3) (signal source acc. to p0849) present
o10.1 Voltage disconnect (OFF2) (signal source acc. to p0844) pending
o10.2 Voltage disconnect (OFF2) (signal source acc. to p0845) pending
o10.3 E stop (safety shutdown) (terminal 105/106) pending
o10.6 CUD right
o11.0 Fault
o12.0 Initializ. of line voltage sensing for field in progress
o12.1 Initializ. of line voltage sensing for armature in progr.
o12.3 Read out data from gating modules (armature and field)
378
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 1
Func. diagram: 2651, 6905
Unit selection: -
Expert list: 1