2 Parameters
2.2 List of parameters
p50112[0...n]

Field circuit resistance / R_field circuit

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.000 [ohm]
Description:
Sets the field circuit resistance.
Note:
The parameter is set automatically during the optimization run for closed-loop field current control (p50051 = 24).
p50113[0...n]

Motor I2t monitoring continuous current factor / Mot I2t I_cont

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.50
Description:
Sets the permissible continuous armature current for motor I2t monitoring.
Note:
At this permissible continuous current, fault F60037 is not output.
The current is calculated as follows: p50113 * p50100.
p50114[0...n]

Motor thermal time constant / Mot T therm

DC_CTRL
Can be changed: C2(1), U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0 [s]
Description:
Sets the thermal time constant of the motor.
Note:
Value = 0:
The motor's I2t monitoring is de-activated.
p50115[0...n]

Speed controller EMF at maximum speed / EMF at n_max

DC_CTRL
Can be changed: C2(1), U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
1.00 [%]
Description:
Setting of the percentage value in relation to p50078[0] for specifying the EMF at maximum speed.
The speed is adjusted using the EMF as the speed actual value.
p50116[0...n]
Field circuit inductance / L_field circuit
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.0 [mH]
Description:
Sets the field circuit inductance.
Dependency:
Refer to: p51597
402
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
4000.000 [ohm]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
2.00
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10000 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
140.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1000000.0 [mH]
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 3
Func. diagram: 6910
Unit selection: -
Expert list: 1
Factory setting
0.000 [ohm]
Access level: 2
Func. diagram: 8038
Unit selection: -
Expert list: 1
Factory setting
1.00
Access level: 1
Func. diagram: 8038
Unit selection: -
Expert list: 1
Factory setting
600 [s]
Access level: 1
Func. diagram: 6810
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 3
Func. diagram: 6910
Unit selection: -
Expert list: 1
Factory setting
0.0 [mH]