2 Parameters
2.2 List of parameters
p50389[0...n]
Messages for setpoint/actual value deviation 1 hysteresis / Set/act 1 hyst
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [%]
Description:
Sets the hysteresis for the "Setpoint/actual value deviation 1 reached" message.
The message is triggered when the threshold is overshot.
Once the value falls below the threshold minus the hysteresis, the message is withdrawn.
Dependency:
Refer to: p50388, p50390, p50590, p50591, r53025
Refer to: F60031
p50390[0...n]
Messages for setpoint/actual value deviation 1 OFF delay / Set/act t_OFF
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.0 [s]
Description:
Sets the OFF delay for the "Setpoint/actual value deviation 1 reached" message.
Dependency:
Refer to: p50388, p50389, p50590, p50591, r53025
Refer to: F60031
p50394[0...n]
Messages for field current threshold minimum threshold / Msg If min thresh
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [%]
Description:
Sets the threshold for the "Field current threshold minimum" message.
Dependency:
Refer to: p50395, r53026
Note:
This threshold also affects the phase logic execution in the context of the Direction reversal by field reversal and
Braking by field reversal functions.
The "Field current threshold minimum" message is displayed via r53026.0.
p50395[0...n]
Messages for field current threshold minimum hysteresis / Msg If min hyst
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [%]
Description:
Sets the hysteresis for the "Field current threshold minimum" message.
The message is triggered when the threshold is undershot.
Once the value rises above the threshold plus the hysteresis, the message is withdrawn.
Dependency:
Refer to: r53026
Note:
The "Field current threshold minimum" message is displayed via r53026.0.
450
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.0 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
100.00 [%]
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 8020
Unit selection: -
Expert list: 1
Factory setting
1.00 [%]
Access level: 2
Func. diagram: 8020
Unit selection: -
Expert list: 1
Factory setting
3.0 [s]
Access level: 2
Func. diagram: 8025
Unit selection: -
Expert list: 1
Factory setting
3.00 [%]
Access level: 2
Func. diagram: 8025
Unit selection: -
Expert list: 1
Factory setting
1.00 [%]