Bi: Motor Interface Signal Source For Bearing Condition; Bi: Motor Interface Signal Source For Motor Fan / Mot Mot Fan Sig S; Bi: Motor Interface Signal Source For Motor Temperature; Motor Interface Temperature Sensor / Mot Temp Sensor - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p50487
BI: Motor interface signal source for bearing condition / Mot brg cond sig s
DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for triggering fault F60026 "Bearing condition".
Dependency:
Refer to: r53120
Refer to: F60026
Note:
The fault is triggered with a delay.
The signal is available via binector output r53120.1 for further interconnection.
p50488

BI: Motor interface signal source for motor fan / Mot mot fan sig s

DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for triggering fault F60027 "Motor fan".
Dependency:
Refer to: r53120
Refer to: F60027
Note:
The fault is triggered with a delay.
The signal is available via binector output r53210.0 for further interconnection.
p50489
BI: Motor interface signal source for motor temperature / Mot mot temp sig s
DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for triggering fault F60028 "Motor temperature".
Dependency:
Refer to: r53120
Refer to: F60028
Note:
The fault is triggered with a delay.
The signal is available via binector output r53210.3 for further interconnection.
p50490

Motor interface temperature sensor / Mot temp sensor

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the temperature sensor for monitoring the motor temperature.
Value:
0:
1:
2:
3:
4:
5:
466
No sensor
KTY84
PTC thermistor R_rated 600
PTC thermistor R_rated 1200
PTC thermistor R_rated 1330
PTC thermistor R_rated 2660
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
8
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 8035
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8035
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8035
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8030
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS DCM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents