4 Faults and alarms
4.2 List of faults and alarms
Remedy:
At least one drive to be connected must be specified in p4815.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02007

Function generator: Drive not SERVO / VECTOR / DC_CTRL

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The drive object specified for connection is not a SERVO / VECTOR or DC_CTRL.
Remedy:
Use a SERVO / VECTOR / DC_CTRL drive object with the corresponding number.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02008

Function generator: Drive specified a multiple number of times

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The drive object specified for connection is already specified.
Alarm value (r2124, interpret decimal):
Drive object number of the drive object that is specified a multiple number of times.
Remedy:
Specify a different drive object.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02009

Function generator: Illegal mode

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The set operating mode (p1300) of the drive object is not permissible when using the function generator.
Alarm value (r2124, interpret decimal):
Number of the drive object involved.
Remedy:
Change the operating mode for this drive object to p1300 = 20 (encoderless speed control) or p1300 = 21 (speed
control with encoder).
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.