Bi: Rfg Signal Source For Accepting Setting Value / Rfg Accept Set V; Bi: Bypass Ramp-Function Generator Signal Source / Bypass Rfg Sig S; Ci: Setpoint Processing Sig Source For Pos Limiting Of Main Setpoint; Ci: Setpoint Processing Sig Source For Neg Limiting Of Main Setpoint - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Dependency:
The setting value for the ramp-function generator output is selected via binector input p50640.
p50640 = 0 signal:
If the machine is not running, the value supplied via connector input p50639[1] is accepted.
p50640 = 1 signal:
The value supplied via connector input p50639[0] is accepted as the setting value.
Refer to: p50640
p50640[0...n]

BI: RFG signal source for accepting setting value / RFG accept set v

DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for accepting the setting value of the ramp-function generator.
Dependency:
Refer to: p50639
p50641[0...n]

BI: Bypass ramp-function generator signal source / Bypass RFG sig s

DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for "Bypass ramp-function generator".
Note:
The "Bypass ramp-function generator" signal can also be set via binector input p50649[0 to 2].
p50642[0...3]
CI: Setpoint processing sig source for pos limiting of main setpoint / M set lim p sig s
DC_CTRL
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for variable positive limiting of the main setpoint.
Notice:
Negative values at the selected parameters generate a negative maximum value at the limiting output.
Note:
The minimum of the values set via index 0 to 3 is applied as the limit.
p50643[0...3]
CI: Setpoint processing sig source for neg limiting of main setpoint / M set lim n sig s
DC_CTRL
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for variable positive limiting of the main setpoint.
Notice:
Positive values at the selected parameters generate a positive minimum value at the limiting output.
Note:
The maximum of the values set via index 0 to 3 is applied as the limit.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 3152
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 3152
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 3135
Unit selection: -
Expert list: 1
Factory setting
52002[0]
Access level: 3
Func. diagram: 3135
Unit selection: -
Expert list: 1
Factory setting
[0] 52184[0]
[1] 52185[0]
[2] 52186[0]
[3] 52187[0]
493