Trace: Time slice clock cycle invalid

Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The time slice clock cycle selected does not match any of the existing time slices.
See also: p4723 (Trace time slice cycle)
Remedy:
Enter an existing time slice clock cycle. The existing time slices can be read out via p7901.
See also: r7901 (Sampling times)
A02058

Trace: Time slice clock cycle for endless trace not valid

Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected time slice clock cycle cannot be used for the endless trace
See also: p4723 (Trace time slice cycle)
Remedy:
Enter the clock cycle of an existing time slice with a cycle time >= 2 ms for up to 4 recording channels or >= 4 ms
from 5 recording channels per trace.
The existing time slices can be read out via p7901.
See also: r7901 (Sampling times)
A02059

Trace: Time slice clock cycle for 2 x 8 recording channels not valid

Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected time slice clock cycle cannot be used for more than 4 recording channels.
See also: p4723 (Trace time slice cycle)
Remedy:
Enter the clock cycle of an existing time slice with a cycle time >= 4 ms or reduce the number of recording channels
to 4 per trace.
The existing time slices can be read out via p7901.
See also: r7901 (Sampling times)
A02060

Trace: Signal to be traced missing

Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
- a signal to be traced was not specified.
- the specified signals are not valid.
See also: p4730 (Trace record signal 0), p4731 (Trace record signal 1), p4732 (Trace record signal 2), p4733 (Trace
record signal 3)
Remedy:
- specify the signal to be traced.
- check whether the relevant signal can be traced.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms
935