Remedy:
- Check the power supply of the power unit.
- carry out a POWER ON (power off/on) for the component.
A30041 (F)

Power unit: Undervolt 24/48 V alarm

Message value:
Channel: %1, voltage: %2 [0.1 V]
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the power unit power supply, the lower threshold has been violated.
Alarm value (r2124, interpret hexadecimal):
yyxxxx hex: yy = channel, xxxx = voltage [0.1 V]
yy = 0: 24 V power supply
yy = 1: 48 V power supply
Remedy:
- Check the power supply of the power unit.
- carry out a POWER ON (power off/on) for the component.
Reaction upon F:
NONE (OFF1, OFF2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
A30042

Power unit: Fan has reached the maximum operating hours

Message value:
%1
Message class:
Power electronics faulted (5)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum operating time of at least one fan will soon be reached, or has already been exceeded.
Fault value (r0949, interpret binary):
Bit 0: heat sink fan will reach the maximum operating time in 500 hours.
Bit 1: heat sink fan has exceeded the maximum operating time.
Bit 8: internal device fan will reach the maximum operating time in 500 hours.
Bit 9: internal device fan has exceeded the maximum operating time.
Note:
The maximum operating time of the heat sink fan in the power unit is displayed in p0252.
The maximum operating time of the internal device fan in the power unit is internally specified and is fixed.
Remedy:
For the fan involved, carry out the following:
- replace the fan.
- reset the operating hours counter (p0251, p0254).
F30043

Power unit: Overvolt 24/48 V

Message value:
Channel: %1, voltage: %2 [0.1 V]
Message class:
Supply voltage fault (undervoltage) (3)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
For the power unit power supply, the upper threshold has been violated.
Fault value (r0949, interpret hexadecimal):
yyxxxx hex: yy = channel, xxxx = voltage [0.1 V]
yy = 0: 24 V power supply
yy = 1: 48 V power supply
Remedy:
Check the power supply of the power unit.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms
979