Thyristor Diagnostics Mode / Thyr_Diag Mode - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Analog input XT1.103/104 - 270 V
[28] = Compensation value at 0 V
[29] = Compensation value at +270 V
[30] = Compensation value at -270 V
[31] = Compensation value at reference value
Analog input 3 - X177.1/2
[32] = Compensation value at 0 V
[33] = Compensation value at +10 V
[34] = Compensation value at -10 V
[35] = Compensation value at reference value
Analog input 4 - X177.3/4
[36] = Compensation value at 0 V
[37] = Compensation value at +10 V
[38] = Compensation value at -10 V
[39] = Compensation value at reference value
Analog input 5 - X177.5/6
[40] = Compensation value at 0 V
[41] = Compensation value at +10 V
[42] = Compensation value at -10 V
[43] = Compensation value at reference value
Analog input 6 - X177.7/8
[44] = Compensation value at 0 V
[45] = Compensation value at +10 V
[46] = Compensation value at -10 V
[47] = Compensation value at reference value
Analog output 0 - X177.49/50
[48] = Compensation value for 0 V
[49] = Compensation value for +10 V
[50] = Compensation value for -10 V
[51] = Compensation value for reference value
Analog output 1 - X177.51/52
[52] = Compensation value for 0 V
[53] = Compensation value for +10 V
[54] = Compensation value for -10 V
[55] = Compensation value for reference value
The compensation values for analog outputs 0 and 1, as well as for analog inputs 3 to 6, are calculated from the
measurement result + an offset of 32768.
p50830

Thyristor diagnostics mode / Thyr_diag mode

DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the thyristor diagnostics mode.
Value = 0:
The thyristor test is de-activated.
Value = 1:
The thyristors are tested when first switching on or jogging after the electronics power supply has been switched on.
Value = 2:
The thyristors are tested at each switch-on or jogging.
Value = 3:
The thyristors are tested at the next switch-on or jogging. p50830 is set to 0 if the test was completed error-free.
524
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 6865
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS DCM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents