p50396[0...n]

Field current monitoring setpoint factor / If_mon set_fact

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
1 [%]
Description:
Sets the factor for the setpoint in the context of field current monitoring.
Dependency:
Refer to: p50265, p50397
Refer to: F60005
p50397[0...n]

Field current monitoring fault delay time / If_mon F t_del

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.02 [s]
Description:
Sets the delay time for triggering fault F60005 in the context of field current monitoring.
Dependency:
Refer to: p50265, p50396
Refer to: F60005
p50398[0...n]
Messages for field current actual value less than setpoint fact / Msg If<set fact
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [%]
Description:
Sets the factor for the setpoint for the "Field current actual value less than setpoint" message.
Dependency:
Refer to: p50399, r53026
Note:
This threshold also affects the phase logic execution in the context of the Direction reversal by field reversal and
Braking by field reversal functions.
The "Field current actual value less than setpoint" message is displayed via r53026.1.
p50399[0...n]
Messages for field current actual value less than setpoint hyst / Msg If<set hyst
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [%]
Description:
Sets the hysteresis for the "Field current actual value less than setpoint" message.
The message is triggered when the threshold is undershot (setpoint x factor).
Once the value rises above the threshold (setpoint x factor) plus the hysteresis, the message is withdrawn.
Dependency:
Refer to: p50398, r53026
Note:
The "Field current actual value less than setpoint" message is displayed via r53026.1.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
100 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
60.00 [s]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
100.00 [%]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8044
Unit selection: -
Expert list: 1
Factory setting
50 [%]
Access level: 2
Func. diagram: 8044
Unit selection: -
Expert list: 1
Factory setting
0.50 [s]
Access level: 2
Func. diagram: 8025
Unit selection: -
Expert list: 1
Factory setting
80.00 [%]
Access level: 2
Func. diagram: 8025
Unit selection: -
Expert list: 1
Factory setting
1.00 [%]