Ci: Line Zero Crossings Offset Angle Thyristor Pair-Dependent S_Src; Current Actual Value Sensing Analog Input Configuration; Current Actual Value Sensing Analog Input Voltage At Rated Ia - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

p51847[0...5]
CI: Line zero crossings offset angle thyristor pair-dependent s_src / Line offset s_src
DC_CTRL
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the offset angle dependent on a thyristor pair between the line zero crossings at the power
unit and the synchronizing voltage.
Index:
[0] = Thyristor pair 1-6 (UV+)
[1] = Thyristor pair 1-2 (WU-)
[2] = Thyristor pair 2-3 (VW+)
[3] = Thyristor pair 3-4 (UV-)
[4] = Thyristor pair 4-5 (WU+)
[5] = Thyristor pair 5-6 (VW-)
Dependency:
Refer to: p51845, p51846
p51852
Current actual value sensing analog input configuration / I_sens AI config
DC_CTRL
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the configuration for the armature current actual value sensing.
Value = 0:
The device-internal armature current actual value sensing is active.
Value > 0:
An external armature currrent actual value sensing is fed to the SINAMICS DC MASTER via an analog input. The
device-internal armature current actual value sensing is not active.
Value:
0:
1:
2:
3:
4:
Dependency:
Refer to: p51823, p51824
Danger:
For value > 0, the following applies:
Incorrect setting of parameter p51853 leads to damaging or destruction of the power unit!
Note:
For value > 0, the following applies:
This is to be used only in certain special cases, where the accuracy of the device-internal armature current actual
value sensing is regarded as insufficient.
The following applies for the Control Module:
p51852 = 0: p51824 is active
p51852 > 0: p51824 is not active
p51853
Current actual value sensing analog input voltage at rated Ia / I_sen AI V at Ia
DC_CTRL
Can be changed: T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.100 [V]
Description:
Sets the voltage for the external current actual value sensing.
This voltage is supplied via the input terminal X177:x/x at armature rated current.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Ia sensing internal
Sensing via analog input 3 (X177.1/2)
Sensing via analog input 4 (X177.3/4)
Sensing via analog input 5 (X177.5/6)
Sensing via analog input 6 (X177.7/8)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
4
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
10.000 [V]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 6950
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 2
Func. diagram: 6850
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 6850
Unit selection: -
Expert list: 1
Factory setting
5.000 [V]
557