2 Parameters
2.2 List of parameters
Dependency:
Refer to: p0700, p1000, p1500, r8570
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
When executing a specific macro, the corresponding programmed settings are made and become active.
Note:
The macros in the specified directory are displayed in r8570. r8570 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
p0015

Macro drive object / Macro DO

DC_CTRL,
Can be changed: C2(1)
DC_CTRL_R,
Data type: Unsigned32
DC_CTRL_R_S,
P-Group: Commands
DC_CTRL_S, TM150,
Not for motor type: -
TM15DI_DO, TM31
Min
0
Description:
Runs the corresponding macro files.
The selected macro file must be available on the memory card/device memory.
Example:
p0015 = 6 --> the macro file PM000006.ACX is run.
Dependency:
Refer to: p0700, p1000, p1500, r8570
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
When executing a specific macro, the corresponding programmed settings are made and become active.
No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
Note:
The macros in the specified directory are displayed in r8570. r8570 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
p0016

Activate BOP user-defined list / BOP user list act

CU_DC, CU_DC_R,
Can be changed: C1, U, T
CU_DC_R_S,
Data type: Integer16
CU_DC_S
P-Group: -
Not for motor type: -
Min
0
Description:
Setting for activating/de-activating the user-defined list for the Basic Operator Panel (BOP).
If p0016 = 1, then it is only possible to access parameters in the parameter list (p0013).
Value:
0:
1:
Dependency:
Refer to: p0011, p0012, p0013
Note:
The user-defined list can only be de-activated with p0011 = p0012
r0018

Control Unit basic firmware version / CU Basic FW Vers

CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Unsigned32
CU_DC_S
P-Group: -
Not for motor type: -
Min
0
Description:
Displays the basic firmware version of the Control Unit.
The version of existing firmware on the device memory is displayed in r7844.
Dependency:
Refer to: r0148, r0158, r0197, r0198, r7844
Note:
Example:
The value 1010100 should be interpreted as V01.01.01.00.
38
BOP user-defined list de-activated
BOP user-defined list activated
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
999999
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
4294967295
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS DCM