2 Parameters
2.2 List of parameters
Note:
The value is entered in integer (complete) encoder pulses.
For p2720.0 = 1, the value is automatically pre-assigned quarter of the encoder range.
Example:
Quarter of the encoder range = (p0408 * p0421) / 4
It is possible that the tolerance window may not be able to be precisely set due to the data type (floating point number
with 23 bit mantissa).
r2723[0...n]

CO: Load gear absolute value / Load gear abs_val

DC_CTRL,
Can be changed: -
DC_CTRL_R,
Data type: Unsigned32
DC_CTRL_R_S,
P-Group: Encoder
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Displays the absolute value after the load gear.
Notice:
The encoder position actual value must be requested using the encoder control word Gn_STW.13.
Note:
The increments are displayed in the format the same as r0483.
r2724[0...n]

CO: Load gear position difference / Load gear pos diff

DC_CTRL,
Can be changed: -
DC_CTRL_R,
Data type: Integer32
DC_CTRL_R_S,
P-Group: Encoder
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Displays the position difference before the load gear between powering down and powering up.
Note:
The increments are displayed in the same format as for r0483/r2723.
If the measuring gear of the motor encoder is not activated, the position difference should be read in encoder
increments.
If the measuring gear of the motor encoder is activated, the position difference is converted using the measuring gear
factor.
p2810[0...1]

BI: AND logic operation inputs / AND inputs

DC_CTRL,
Can be changed: T
DC_CTRL_R,
Data type: Unsigned32 / Binary
DC_CTRL_R_S,
P-Group: Functions
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Sets the signal sources for the inputs of the AND logic operation.
Dependency:
Refer to: r2811
Note:
[0]: AND logic operation, input 1 --> the result is displayed in r2811.0.
[1]: AND logic operation, input 2 --> the result is displayed in r2811.0.
r2811.0

CO/BO: AND logic operation result / AND result

DC_CTRL,
Can be changed: -
DC_CTRL_R,
Data type: Unsigned32
DC_CTRL_R_S,
P-Group: Functions
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Displays the result of the AND logic operation
196
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 1
Func. diagram: 4704
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: 2634
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 2634
Unit selection: -
Expert list: 1
Factory setting
-