Note:
Re bits 00, 01, 02, 04, 05, 06, 09:
For PROFIdrive, these signals are used for status word 1.
p0918

PROFIBUS address / PB address

CU_DC_R,
Can be changed: T
CU_DC_R_S
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
1
Description:
Sets the PROFIBUS address for PROFIBUS interface (X126) on the Control Unit.
The address can be set as follows:
Via p0918
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Note:
Permissible PROFIBUS addresses: 1 ... 126
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
p0918
PROFIBUS address / PB address
CU_DC, CU_DC_S
Can be changed: T
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
1
Description:
Sets the PROFIBUS address for PROFIBUS interface (X126) on the Control Unit.
The address can be set as follows:
Via p0918
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Note:
Permissible PROFIBUS addresses: 1 ... 126
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
p0922

IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr

CU_DC, CU_DC_R,
Can be changed: C2(1), T
CU_DC_R_S,
Data type: Unsigned16
CU_DC_S
P-Group: Communications
Not for motor type: -
Min
390
Description:
Sets the send and receive telegram.
Value:
390:
999:
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Controller enable
Control request
Pulses enabled
Open holding brake
Command close holding brake
Pulse enable from the brake control
Setpoint enable from the brake control
SIEMENS telegram 390, PZD-2/2
Free telegram configuration with BICO
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
126
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
126
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
999
2 Parameters
2.2 List of parameters
No
No
No
No
No
No
No
Access level: 2
Func. diagram: 1520, 2410
Unit selection: -
Expert list: 1
Factory setting
125
Access level: 2
Func. diagram: 1520, 2410
Unit selection: -
Expert list: 1
Factory setting
126
Access level: 1
Func. diagram: 1520, 2420
Unit selection: -
Expert list: 1
Factory setting
999
-
-
-
-
-
-
-
105