Cud Analog Output 0 Signal Processing / Cud Ao 0 Sig Proc; Cud Analog Output 0 Smoothing Time Constant / Cud Ao 0 T; Cud Analog Output 0 Scaling / Cud Ao 0 Scal; Cud Analog Output 0 Offset / Cud Ao 0 Offs - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Note:
AO: Analog Output
p50751

CUD analog output 0 signal processing / CUD AO 0 sig proc

DC_CTRL
Can be changed: U, T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the mode for signal processing at analog output 0 (X177.49/50).
Value:
0:
1:
2:
3:
p50752

CUD analog output 0 smoothing time constant / CUD AO 0 T

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0 [ms]
Description:
Sets the time constant for smoothing the signal from analog output 0 (X177.49/50).
p50753

CUD analog output 0 scaling / CUD AO 0 scal

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-200.00 [V]
Description:
Sets the scaling for analog output 0 (X177.49/50).
The value indicates the output value for the mapping of an input value of 100% at the analog output.
Note:
Example:
p50753 = 5 V
--> 100% is scaled to 5 V
--> 50% corresponds to 2.5 V
p50754

CUD analog output 0 offset / CUD AO 0 offs

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-10.00 [V]
Description:
Sets the offset for analog output 0 (X177.49/50).
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Signal not controlled
Signal absolute value generation
Signal inverted
Signal absolute value generation inverted
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
10000 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
200.00 [V]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
10.00 [V]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 2095
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 2095
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 2
Func. diagram: 2095
Unit selection: -
Expert list: 1
Factory setting
10.00 [V]
Access level: 2
Func. diagram: 2095
Unit selection: -
Expert list: 1
Factory setting
0.00 [V]