Motor I2T Monitoring Starting Behavior / Mot I2T Strt Behav; Armature Converter Alpha W Limit (Single-Phase Operation); Armature Converter Correction Angle Alpha W Limit / Arm Corr Alpha W; Armature Converter Alpha G Limit / Arm Alpha G Lim - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

p50140

Motor I2t monitoring starting behavior / Mot I2t strt behav

DC_CTRL
Can be changed: U, T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
2
Description:
Sets the starting behavior for I2t monitoring of the motor.
Value:
2:
12:
Note:
If value = 12:
For motor I2t monitoring, when switching off, the model temperature is saved in a non-volatile fashion. When
switching on, the saved value is taken into account in the model calculation. As a consequence, the UL508C
specification is fulfilled.
p50148[0...n]
Armature converter Alpha W limit (single-phase operation) / A Alpha W lim 1-ph
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
120.0 [°]
Description:
Sets the inverter stability limit for the firing angle of the armature converter in single-phase operation.
Dependency:
Refer to: r53190
Note:
The status of the Alpha W limit is shown in r53190.8.
p50149[0...n]

Armature converter correction angle Alpha W limit / Arm corr Alpha W

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-60.0 [°]
Description:
Setting of the correction angle for current-dependent offset of the Alpha W limit.
p50150[0...n]

Armature converter Alpha G limit / Arm Alpha G lim

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.0 [°]
Description:
Sets the rectifier stability limit for the firing angle of the armature converter.
Dependency:
Refer to: r53190
Note:
The status of the Alpha G limit is shown in r53190.7.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Start I2t with zero
Start I2t with saved value
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
12
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
180.0 [°]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
0.0 [°]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
165.0 [°]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8038
Unit selection: -
Expert list: 1
Factory setting
12
Access level: 3
Func. diagram: 6860
Unit selection: -
Expert list: 1
Factory setting
178.0 [°]
Access level: 3
Func. diagram: 6860
Unit selection: -
Expert list: 1
Factory setting
0.0 [°]
Access level: 3
Func. diagram: 6860
Unit selection: -
Expert list: 1
Factory setting
30.0 [°]
409

Hide quick links:

Advertisement

Table of Contents
loading