p0101[0...n]

Drive object numbers / DO numbers

CU_DC, CU_DC_R,
Can be changed: C1(1)
CU_DC_R_S,
Data type: Unsigned16
CU_DC_S
P-Group: Topology
Not for motor type: -
Min
0
Description:
The parameter contains the object number via which every drive object can be addressed.
The number of an existing drive object is entered into each index.
Value = 0: No drive object is defined.
Note:
The numbers are automatically allocated.
For the commissioning software, this object number cannot be entered using the expert list, but is automatically
assigned when inserting an object.
r0102[0...1]

Number of drive objects / DO count

CU_DC, CU_DC_R,
Can be changed: -
CU_DC_R_S,
Data type: Unsigned16
CU_DC_S
P-Group: Topology
Not for motor type: -
Min
-
Description:
Displays the number of existing or existing and prepared drive objects.
Index:
[0] = Existing drive objects
[1] = Existing and prepared drive objects
Dependency:
Refer to: p0101
Note:
The numbers of the drive objects are in p0101.
Index 0:
Displays the number of drive objects that have already been set up.
Index 1:
Displays the number of drive objects that have already been set up and, in addition, the drive objects that still have to
be set up.
p0103[0...n]

Application-specific view / Appl_spec view

CU_DC, CU_DC_R,
Can be changed: C1(2)
CU_DC_R_S,
Data type: Unsigned16
CU_DC_S
P-Group: -
Not for motor type: -
Min
0
Description:
The application-specific view of an existing drive object is entered into each index.
The parameter cannot be changed.
Dependency:
Refer to: p0107, r0107
Note:
The application-specific views are defined in files on the memory card with the following structure:
PDxxxyyy.ACX
xxx: Application-specific view (p0103)
yyy: Type of drive object (p0107)
Example:
PD052017.ACX
--> "017" stands for the drive object of type DC_CTRL
--> "052" is the number of the view for this drive object
46
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
62
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
999
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0