2 Parameters
2.2 List of parameters
p4059[0...1]

TM31 analog inputs characteristic value x2 / TM31 AI char x2

TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-20.000
Description:
Sets the scaling characteristic for the analog inputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (input voltage in V or input current in mA) of the 2nd value pair of the
characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The unit of this parameter (V or mA) depends on the analog input type.
Refer to: p4056
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not have a limiting effect.
p4060[0...1]

TM31 analog inputs characteristic value y2 / TM31 AI char y2

TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog inputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not have a limiting effect.
p4061[0...1]

TM31 analog inputs wire breakage monitoring response threshold /

TM31 WireBrkThresh
TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
0.00 [mA]
Description:
Sets the response threshold for wire-breakage monitoring of the analog inputs of Terminal Module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
For the following analog input type, the wire breakage monitoring is active:
p4056[x] = 3 (unipolar current input monitored (+4 mA ... +20 mA))
Refer to: p4056
226
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
20.000
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000.00 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
20.00 [mA]
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
10.000
Access level: 2
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 2
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
2.00 [mA]
SINAMICS DCM