Topology: Serial Number Different; Topology: Incorrect Connection Used - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
Remedy:
Adapting topologies:
- connect the expected component (correct the actual topology).
- adapt the project/parameterization in the commissioning software (correct the target topology).
Topology comparison - if required, adapt the comparison level:
- parameterize the topology comparison of all components (p9906).
- parameterize the topology comparison of one components (p9907, p9908).
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
A01425

Topology: Serial number different

Message value:
Component: %1, %2, differences: %3
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected differences in the actual and target topologies in relation to one component.
The serial number is different.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = reserved
cc = number of differences (%3)
bb = component class (% 2)
aa = component number (%1)
Note:
The component class is described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy:
Adapting topologies:
- change over the actual topology to match the target topology.
- download the target topology that matches the actual topology (commissioning software).
Re byte cc:
cc = 1 --> can be acknowledged using p9904 or p9905.
cc > 1 --> can be acknowledged using p9905 and can be de-activated using p9906 or p9907/p9908.
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
See also: p9904 (Topology comparison acknowledge differences), p9905 (Device specialization), p9906 (Topology
comparison comparison stage of all components), p9907 (Topology comparison comparison stage of the component
number), p9908 (Topology comparison comparison stage of a component)
A01428

Topology: Incorrect connection used

Message value:
Component: %1, %2, connection (actual): %3, connection (target): %4
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected differences in the actual and target topologies in relation to one component.
For a component, another connection was used.
The different connections of a component are described in the alarm value.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number of the target topology (%4)
cc = connection number of the actual topology (%3)
bb = component class (% 2)
aa = component number (%1)
912
List Manual (LH8), 02/2015, 6RX1800-0ED76
SINAMICS DCM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents