2.2 List of parameters
p50644[0...n]

CI: Setpoint processing signal source for main setpoint / M set sig s

DC_CTRL
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the main setpoint in the context of setpoint processing.
Dependency:
Refer to: p50320, p50322
p50645[0...n]
CI: Setpoint processing signal source for additional setpoint / A set sig s
DC_CTRL
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the additional setpoint in the context of setpoint processing.
Dependency:
Refer to: p50321, p50323
p50646[0...n]
BI: RFG signal source for ramp-up integrator enable / R-up int ena sig s
DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for enabling the ramp-up integrator on the ramp-function generator.
p50647[0...n]

BI: RFG tracking activation signal source / RFG trck act sig s

DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for activating/de-activating ramp-function generator tracking.
Dependency:
The enable for ramp-function generator tracking must be available (p50317 = 1).
Refer to: p50317
p50648
CI: RFG signal source for input signal / RFG inp sig sig s
DC_CTRL
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the ramp-function generator's input signal.
494
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
-
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 3
Func. diagram: 3135
Unit selection: -
Expert list: 1
Factory setting
52206[0]
Access level: 3
Func. diagram: 3135
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 3150
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 3152
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 3151
Unit selection: -
Expert list: 1
Factory setting
52193[0]