Tm31 Fault Threshold/Alarm Threshold / Tm31 F/A_Thresh; Tm150 Delay Time / Tm150 T_Delay - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

[16] = Channel 8 alarm threshold (A35414)
[17] = Channel 8 fault threshold (F35404)
[18] = Channel 9 alarm threshold (A35415)
[19] = Channel 9 fault threshold (F35405)
[20] = Channel 10 alarm threshold (A35416)
[21] = Channel 10 fault threshold (F35406)
[22] = Channel 11 alarm threshold (A35417)
[23] = Channel 11 fault threshold (F35407)
Dependency:
Refer to: p4103, r4104, r4105, p4118
Notice:
Faults F35207 ... F35210 and F35400 ... F35407 only result in the drive being shut down if at least one BICO
interconnection exists between the drive and the TM150.
For p4102[0...23] = 251 °C, evaluation of the corresponding threshold is deactivated.
For sensor type "PTC thermistor" (p4100[0...11] = 1), the following applies:
To activate the corresponding alarm or fault, p4102[0...23] must be set <= 250 °C.
Note:
The hysteresis can be set in p4118[0...11].
p4102[0...1]

TM31 fault threshold/alarm threshold / TM31 F/A_thresh

TM31
Can be changed: U, T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
-48 [°C]
Description:
Sets the fault threshold/alarm threshold for Terminal Module 31 (TM31).
A35211 is initiated, if the temperature actual value r4105[0] > p4102[0]
F35207 is initiated if the temperature actual value r4105[0] > p4102[1] or timer p4103[0] has expired
For alarm A35211 the following applies:
- Remains until the temperature actual value (r4105) reaches or falls below the value (p4102[0] - hysteresis).
For fault F35207 the following applies:
- Remains until the temperature actual value (r4105) reaches or falls below the value (p4102[1] - hysteresis) and the
fault has been acknowledged.
- The hysteresis value is 5 K and cannot be changed by the user.
Index:
[0] = Alarm threshold
[1] = Fault threshold
Dependency:
Refer to: r4104
Notice:
Fault F35207 only causes the drive to be shut down if there is at least one BICO interconnection between the drive
and TM31.
For p4102[0...1] = 251 °C, evaluation of the corresponding threshold is deactivated.
For sensor type "PTC thermistor" (p4100 = 1), the following applies:
To activate the alarm or fault, p4102[0...1] must be set <= 250 °C.
p4103[0...11]

TM150 delay time / TM150 t_delay

TM150
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.0 [s]
Description:
Sets the delay time for the output of the fault for the Terminal Module 150 (TM150).
The timer is started when the alarm threshold (e.g. p4102[0]) is exceeded.
If the delay time has expired and the alarm threshold has, in the meantime, not been fallen below, then the
corresponding fault is output.
The fault can be acknowledged, if, after the delay time has expired, the alarm threshold is again fallen below.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
251 [°C]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
600.0 [s]
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: 9576
Unit selection: -
Expert list: 1
Factory setting
[0] 100 [°C]
[1] 120 [°C]
Access level: 1
Func. diagram: 9626, 9627
Unit selection: -
Expert list: 1
Factory setting
0.0 [s]
241