2 Parameters
2.2 List of parameters
p2200[0...n]

BI: Technology controller enable / Tec_ctrl enable

DC_CTRL (Tech_ctrl),
Can be changed: T
DC_CTRL_R
Data type: Unsigned32 / Binary
(Tech_ctrl),
P-Group: Technology
DC_CTRL_R_S
Not for motor type: -
(Tech_ctrl),
DC_CTRL_S
Min
(Tech_ctrl)
-
Description:
Sets the signal source to switch in/switch out the technology controller.
The technology controller is switched in with a 1 signal.
p2252

Technology controller configuration / Tec_ctrl config

DC_CTRL (Tech_ctrl),
Can be changed: U, T
DC_CTRL_R
Data type: Unsigned16
(Tech_ctrl),
P-Group: Modulation
DC_CTRL_R_S
Not for motor type: -
(Tech_ctrl),
DC_CTRL_S
Min
(Tech_ctrl)
-
Description:
Sets the configuration of the technology controller.
Bit field:
Bit
00
01
02
03
Dependency:
Refer to: p2257, p2258, p2267, p2268, p2280, p2285
Note:
Re bit 00 = 0:
The ramp-down time (p2258) switches to the ramp-up time (p2257) when the sign for the output signal r2260
changes. When the sign changes, the output signal is kept at zero for one arithmetic cycle.
Re bit 00 = 1:
When r2260 exhibits a positive gradient, the ramp-up time (p2257) is active; when it exhibits a negative gradient, the
ramp-down time (p2258) is active. The sign for r2260 does not have any effect on the ramp time.
Re bit 01 = 0:
The integration time of the PID controller is evaluated with the gain factor Kp (p2280) (p2285 = integral time).
Re bit 01 = 1:
The integration time of the PID controller is independent of the gain factor (p2285 = integration time) if p2280 > 0.
Re bit 02 = 0:
When the PID controller is de-activated via p2200, the output signal r2294 is reduced to zero via the ramp-down time
p2293.
Re bit 02 = 1:
When the PID controller is de-activated via p2200, the output signal r2294 is set directly to zero.
Re bit 03 = 0:
The actual values are not limited by p2267 and p2268.
Re bit 03 = 1:
The actual values are limited by p2267 and p2268.
p2253[0...n]

CI: Technology controller setpoint 1 / Tec_ctrl setp 1

DC_CTRL (Tech_ctrl),
Can be changed: U, T
DC_CTRL_R
Data type: Unsigned32 / FloatingPoint32
(Tech_ctrl),
P-Group: Technology
DC_CTRL_R_S
Not for motor type: -
(Tech_ctrl),
DC_CTRL_S
Min
(Tech_ctrl)
-
Description:
Sets the signal source for the setpoint 1 of the technology controller.
Dependency:
Refer to: p2254, p2255
182
Signal name
Ramp-up/down time independent of
setpoint sign
Integrator independent of Kp
Output signal without ramp active
Actual value limiting
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: PERCENT
Max
-
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0111 bin
0 signal
No
No
No
No
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS DCM