2 Parameters
2.2 List of parameters
p0848[0...n]

BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1

DC_CTRL,
Can be changed: T
DC_CTRL_R,
Data type: Unsigned32 / Binary
DC_CTRL_R_S,
P-Group: Commands
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Sets the first signal source for the command "No quick stop/quick stop (OFF3)".
The following signals are AND'ed:
- BI: p0848 "No quick stop / quick stop (OFF3) signal source 1"
- BI: p0849 "No quick stop / quick stop (OFF3) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 2 (STW1.2).
BI: p0848 = 0 signal or BI: p0849 = 0 signal
- OFF3 (braking along the OFF3 ramp (p50296), then pulse suppression and switch on inhibit)
BI: p0848 = 1 signal and BI: p0849 = 1 signal
- No OFF3 (enable is possible)
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0849[0...n]

BI: No Quick Stop / Quick Stop (OFF3) signal source 2 / OFF3 S_src 2

DC_CTRL,
Can be changed: T
DC_CTRL_R,
Data type: Unsigned32 / Binary
DC_CTRL_R_S,
P-Group: Commands
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Sets the second signal source for the command "No quick stop/quick stop (OFF3)".
The following signals are AND'ed:
- BI: p0848 "No quick stop / quick stop (OFF3) signal source 1"
- BI: p0849 "No quick stop / quick stop (OFF3) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 2 (STW1.2).
BI: p0848 = 0 signal or BI: p0849 = 0 signal
- OFF3 (braking along the OFF3 ramp (p50296), then pulse suppression and switch on inhibit)
BI: p0848 = 1 signal and BI: p0849 = 1 signal
- No OFF3 (enable is possible)
Caution:
When "master control from PC" is activated, this binector input is effective.
p0852[0...n]

BI: Enable operation/inhibit operation / Operation enable

DC_CTRL,
Can be changed: T
DC_CTRL_R,
Data type: Unsigned32 / Binary
DC_CTRL_R_S,
P-Group: Commands
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "enable operation/inhibit operation".
For the PROFIdrive profile, this command corresponds to control word 1 bit 3 (STW1.3).
BI: p0852 = 0 signal
Inhibit operation (suppress pulses).
BI: p0852 = 1 signal
Enable operation (pulses can be enabled).
102
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 3
Func. diagram: 2580
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2580
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2580
Unit selection: -
Expert list: 1