Cu: Descriptive Data Error; Cu: Configuring Data Invalid; Cu: It Is Not Possible To Write To File; Memory Card And Device Incompatible - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

4 Faults and alarms
4.2 List of faults and alarms
F01044

CU: Descriptive data error

Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An error was detected when loading the descriptive data saved in the non-volatile memory.
Remedy:
Replace the memory card or Control Unit.
A01045

CU: Configuring data invalid

Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
An error was detected when evaluating the parameter files PSxxxyyy.ACX, PTxxxyyy.ACX, CAxxxyyy.ACX, or
CCxxxyyy.ACX saved in the non-volatile memory. Because of this, under certain circumstances, several of the saved
parameter values were not able to be accepted. Also see r9406 up to r9408.
Alarm value (r2124, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- Check the parameters displayed in r9406 up to r9408, and correct these if required.
- Restore the factory setting using (p0976 = 1) and re-load the project into the drive unit.
Then save the parameterization in STARTER using the "Copy RAM to ROM" function or with p0977 = 1. This
overwrites the incorrect parameter files in the non-volatile memory – and the alarm is withdrawn.
A01049

CU: It is not possible to write to file

Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
It is not possible to write into a write-protected file (PSxxxxxx.acx). The write request was interrupted.
Alarm value (r2124, interpret decimal):
Drive object number.
Remedy:
Check whether the "write protected" attribute has been set for the files in the non-volatile memory under
.../USER/SINAMICS/DATA/...
When required, remove write protection and save again (e.g. set p0977 to 1).
F01050

Memory card and device incompatible

Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The memory card and the device type do not match (e.g. a memory card for SINAMICS S is inserted in SINAMICS
G).
Remedy:
- insert the matching memory card.
- use the matching Control Unit or power unit.
F01054
CU: System limit exceeded
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
At least one system overload has been identified.
882
List Manual (LH8), 02/2015, 6RX1800-0ED76
SINAMICS DCM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents