2 Parameters
2.2 List of parameters
r0836.0

CO/BO: Command Data Set CDS selected / CDS selected

DC_CTRL,
Can be changed: -
DC_CTRL_R,
Data type: Unsigned8
DC_CTRL_R_S,
P-Group: Displays, signals
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Displays the command data set (CDS) selected via the binector input.
Bit field:
Bit
00
Dependency:
Refer to: r0050, p0810
Note:
Command data sets are selected via binector input p0810.
The currently effective command data set is displayed in r0050.
r0837.0...1

CO/BO: Drive Data Set DDS selected / DDS selected

DC_CTRL,
Can be changed: -
DC_CTRL_R,
Data type: Unsigned8
DC_CTRL_R_S,
P-Group: Displays, signals
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Displays the drive data set (DDS) selected via the binector input.
Bit field:
Bit
00
01
Dependency:
Refer to: r0051, p0820, p0821
Note:
Drive data sets are selected via binector input p0820 and following.
The currently effective drive data set is displayed in r0051.
p0840[0...n]

BI: ON / OFF (OFF1) / ON / OFF (OFF1)

DC_CTRL,
Can be changed: T
DC_CTRL_R,
Data type: Unsigned32 / Binary
DC_CTRL_R_S,
P-Group: Commands
DC_CTRL_S
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "ON/OFF (OFF1)".
For the PROFIdrive profile, this command corresponds to control word 1 bit 0 (STW1.0).
Recommendation:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
Refer to: p1055, p1056
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
For binector input p0840 = 0 signal, the motor can be moved, jogging using binector input p1055 or p1056.
The command "ON/OFF (OFF1)" can be issued using binector input p0840 or p1055/p1056.
For binector input p0840 = 0 signal, the switch-on inhibit is acknowledged.
Only the signal source that originally powered up can also power down again.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
100
Signal name
CDS select. bit 0
Signal name
DDS select. bit 0
DDS select. bit 1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
ON
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
ON
ON
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
List Manual (LH8), 02/2015, 6RX1800-0ED76
Access level: 3
Func. diagram: 8560
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
OFF
Access level: 2
Func. diagram: 8565
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
OFF
OFF
Access level: 3
Func. diagram: 2580
Unit selection: -
Expert list: 1
Factory setting
1
SINAMICS DCM
FP
-
FP
-
-