Bi: Fixed Setpoint Signal Source For Connector Selection 0; Bi: Fixed Setpoint Signal Source For Connector Selection 1; Bi: Speed Controller Droop Enable / Droop Enable; Bi: Speed Controller Signal Source For Master/Slave Drive - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

p50680[0...n]
BI: Fixed setpoint signal source for connector selection 0 / Fix set con0 sig s
DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the selection of connector 0 (p50431[0]).
Dependency:
Refer to: p50430, p50431
p50681[0...n]
BI: Fixed setpoint signal source for connector selection 1 / Fix set con1 sig s
DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the selection of connector 1 (p50431[1]).
Dependency:
Refer to: p50430, p50431
p50684[0...n]

BI: Speed controller droop enable / Droop enable

DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source to enable droop on the speed controller.
Note:
The following values are multiplied by the droop output dependent upon the signal state:
1 signal: Enable (r50630)
0 signal: No enable (0%)
p50687[0...n]
BI: Speed controller signal source for master/slave drive / Mast/sl sig s
DC_CTRL
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source for the master or slave drive on the speed controller.
Note:
1 signal:
Torque control is active on the slave drive.
0 signal:
Speed control is active on the master drive.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 3115
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 3115
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 6805
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 2
Func. diagram: 6810, 6830
Unit selection: -
Expert list: 1
Factory setting
0
497

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents