Encoder Identification Data Transfer Running; Drive: Motor Encoder Not Ready; Drive: No Sensor Module With Matching Component Number; External Alarm 1 - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Reaction upon F:
NONE (OFF1, OFF2, OFF3)
Acknowl. upon F:
IMMEDIATELY
N07570 (F)

Encoder identification data transfer running

Message value:
-
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
OFF2
Acknowledge:
NONE
Cause:
The encoder type was automatically determined using p0400 = 10100.
This fault causes the pulses to be suppressed - this is necessary to transfer the encoder parameterization to p0400ff.
See also: p0400 (Encoder type selection)
Remedy:
The fault can be acknowledged without any additional measures.
Reaction upon F:
OFF2
Acknowl. upon F:
IMMEDIATELY
F07575

Drive: Motor encoder not ready

Message value:
-
Message class:
Position/speed actual value incorrect or not available (11)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
OFF2 (ENCODER)
Acknowledge:
IMMEDIATELY
Cause:
The motor encoder signals that it is not ready.
- initialization of encoder 1 (motor encoder) was unsuccessful.
- the function "parking encoder" is active (encoder control word G1_STW.14 = 1).
- the encoder interface (Sensor Module) is de-activated (p0145).
- the Sensor Module is defective.
Remedy:
Evaluate other queued faults via encoder 1.
A07580 (F, N)

Drive: No Sensor Module with matching component number

Message value:
Encoder data set: %1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
NONE
Acknowledge:
NONE
Cause:
A Sensor Module with the component number specified in p0141 was not found.
Alarm value (r2124, interpret decimal):
Encoder data set involved (index of p0141).
Remedy:
Correct parameter p0141.
Reaction upon F:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)
Acknowl. upon F:
IMMEDIATELY (POWER ON)
Reaction upon N:
NONE
Acknowl. upon N:
NONE
A07850 (F)

External alarm 1

Message value:
-
Message class:
External measured value / signal state outside the permissible range (16)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The condition for "External alarm 1" is satisfied.
Note:
The "External alarm 1" is initiated by a 1/0 edge via binector input p2112.
See also: p2112 (External alarm 1)
Remedy:
Eliminate the causes of this alarm.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms
959