p50184[0...n]

Torque limiting changeover speed / T lim n_chng

DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.00 [%]
Description:
Sets the changeover speed for torque limit selection.
Dependency:
Refer to: r52166
Note:
If torque limit changeover is selected (p50694 = 1) and the speed (p52166) is higher than the changeover speed set
in p50184, then torque limit 2 (p50182, p50183) is activated in place of torque limit 1 (p50180, p50181).
p50190[0...n]
Cl-loop arm current ctr prectr setpoint smoothing time constant / Ia prec set T
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0 [ms]
Description:
Sets the time constant for smoothing the armature current setpoints at the armature current pre-control input for
closed-loop armature current control.
Note:
The smoothing time constant is used to decouple armature current pre-control from the armature current controller.
p50191[0...n]
Cl-loop arm current ctr curr controller setp sm time constant / Ia ctr set T
DC_CTRL
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0 [ms]
Description:
Sets the time constant for smoothing the armature setpoint for closed-loop armature current control.
Note:
The smoothing time constant is used to decouple armature current pre-control from the armature current controller.
p50192[0...n]

Armature Alpha W limit control word / A Alpha W lim STW

DC_CTRL
Can be changed: U, T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the control word for the Alpha W limit on the armature.
Value:
0:
1:
Note:
If value = 0:
Continuous current: Alpha W limit = parameter p50151
Pulsating current: Alpha W limit = 165 °
If value = 1:
Alpha W limit = parameter p50151
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
Alpha W limit = 165 ° with pulsating armature current
Alpha W limit = p50151
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: PERCENT
Max
120.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10000 [ms]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10000 [ms]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 6825
Unit selection: -
Expert list: 1
Factory setting
0.00 [%]
Access level: 2
Func. diagram: 6855
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 2
Func. diagram: 6855
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 2
Func. diagram: 6860
Unit selection: -
Expert list: 1
Factory setting
0
419