Cu: Memory Card Withdrawn; Cu: Do Not Power Down. File System Being Optimized.; Cu: Insufficient Memory - Siemens SINAMICS DCM List Manual

Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

A01100

CU: Memory card withdrawn

Message value:
-
Message class:
General drive fault (19)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S
Reaction:
NONE
Acknowledge:
NONE
Cause:
The memory card (non-volatile memory) was withdrawn during operation.
Notice:
It is not permissible for the memory card to be withdrawn or inserted under voltage.
Remedy:
- power down the drive system.
- re-insert the memory card that was withdrawn - this card must match the drive system.
- power up the drive system again.
A01104

CU: Do not power down. File system being optimized.

Message value:
-
Message class:
General drive fault (19)
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The file system is currently being optimized in the non-volatile device memory of the Control Unit. This process may
take several minutes.
Notice:
The Control Unit must not be powered down during optimization, as this can lead to user data being lost.
Remedy:
Leave the Control Unit powered up during optimization.
Note:
The alarm disappears automatically once file system optimization is complete.
F01105 (A)

CU: Insufficient memory

Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
All objects
Reaction:
OFF1
Acknowledge:
POWER ON
Cause:
Too many functions have been configured on this Control Unit (e.g. too many drives, function modules, data sets, OA
applications, blocks, etc).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- change the configuration on this Control Unit (e.g. fewer drives, function modules, data sets, OA applications,
blocks, etc).
- use an additional Control Unit.
Reaction upon A:
NONE
Acknowl. upon A:
NONE
F01106
CU: Insufficient memory
Message value:
%1
Message class:
Hardware / software error (1)
Drive object:
DC_CTRL, DC_CTRL_R, DC_CTRL_R_S, DC_CTRL_S, TM150
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
There is not sufficient free memory space available.
Remedy:
Not necessary.
SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
4 Faults and alarms
4.2 List of faults and alarms