Ntp-G72 Provision External Alarms And Controls On The Alarm Interface Controller-International - Cisco ONS 15454 DWDM Installation And Operation Manual

Hide thumbs Also See for ONS 15454 DWDM:
Table of Contents

Advertisement

NTP-G72 Provision External Alarms and Controls on the Alarm Interface Controller-International

To provision up to four virtual wire inputs for external devices, complete
Step 6
device.
Step 7
Click Apply.
Step 8
If you are provisioning external control outputs for external devices, click the External Controls subtab.
Complete the following options for each external control wired to the ONS 15454 backplane:
Step 9
Step 10
To provision additional external controls, complete Steps
Step 11
Click Apply.
Note
Note
Note
Stop. You have completed this procedure.
NTP-G72 Provision External Alarms and Controls on the Alarm
Interface Controller-International
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Cisco ONS 15454 DWDM Installation and Operations Guide, R4.7
7-38
Description—A default description is provided; enter a different description if needed.
Enabled—Check this check box to activate the fields for the alarm input number.
Control Type—Choose the control type from the drop-down list: air conditioner, engine, fan,
generator, heat, light, sprinkler, or miscellaneous.
Trigger Type—Choose a trigger type: a local minor, major, or critical alarm; a remote minor, major,
or critical alarm; or a virtual wire activation.
Description—Enter a description.
If you provision an external alarm to raise upon an open contact before you physically connect
to the ONS equipment, the alarm will raise until you do create the physical connection.
When you provision an external alarm, the alarm object is ENV-IN-nn. The variable nn refers to
the external alarm's number, regardless of the name you assign.
Environmental alarms that you create (and name) should be recorded locally for the NE. Both
the Alarm name and resolution are node-specific.
Use this procedure to create external (environmental) alarms and external
controls for the AIC-I card.
An AIC-I card must be installed in Slot 9.
DLP-G34 Install the AIC or AIC-I Card, page 1-76
As needed
Onsite or remote
Provisioning or higher
Chapter 7
Step 5
for each additional
8
and
9
for each additional device.
Manage Alarms
November 2004

Advertisement