Dlp-G8 Install The Air Ramp - Cisco ONS 15454 DWDM Installation And Operation Manual

Hide thumbs Also See for ONS 15454 DWDM:
Table of Contents

Advertisement

Chapter 1
Install the Shelf and Common Control Cards
Figure 1-5
Repeat this task for every shelf assembly you need to install.
Step 4
Return to your originating procedure (NTP).
Step 5

DLP-G8 Install the Air Ramp

Purpose
Tools/Equipment
Prerequisite Procedures None
Required/As Needed
Onsite/Remote
Security Level
The air ramp requires 1 RU in a standard 19-inch (482.6-mm) or 23-inch (584.2-mm) rack. Locate the
Step 1
RMU space specified in your site plan.See the
page 13-16
Step 2
Verify that the mounting brackets attached to the unit are correct for your rack size. Complete
Reverse the Mounting Bracket to Fit a 19-inch (482.6-mm) Rack (ANSI Only)" task on page 1-10
required.
Align the chassis with the rack mounting screw holes; insert and tighten the four screws.
Step 3
September 2004
Mounting the Air Ramp in a Rack
Equipment rack
Use this task to install the air ramp.
#2 Phillips screwdriver
As needed
Onsite
None
for more information about air ramp placement.
"13.5 Typical DWDM Rack Layouts" section on
Cisco ONS 15454 DWDM Installation and Operations Guide, R4.7
DLP- G8 Install the Air Ramp
"DLP-G3
as
1-19