DLP-G121 Create a New or Cloned Alarm Severity Profile
Step 10
In the New Profile or Clone Profile dialog box, enter a name in the New Profile Name field.
Profile names must be unique. If you try to import or name a profile that has the same name as another
profile, CTC adds a suffix to create a new name. Long file names are supported.
Step 11
Click OK.
A new alarm profile (named in
and appears at the right of the previous profile column in the Alarm Profiles window. You can select it
and drag it to a different position.
Note
The Default profile sets severities to standard Telcordia GR-253-CORE settings. If an alarm has an
Inherited profile, it inherits (copies) its severity from the same alarm's severity at the higher level. For
example, if you choose the Inherited profile from the network view, the severities at the lower levels
(node, card, and port) will be copied from this selection. A card with an Inherited alarm profile copies
the severities used by the node that contains the card. (If you are creating profiles, you can apply these
separately at any level. To do this, refer to the
task on page
Modify (customize) the new alarm profile:
Step 12
In the new alarm profile column, click the alarm severity you want to change in the custom profile.
a.
b.
Choose a severity from the drop-down list.
Repeat Steps
c.
when you view the alarms or conditions after making modifications:
After you have customized the new alarm profile, right-click the profile column to highlight it.
Step 13
Step 14
Click Store.
Step 15
In the Store Profiles dialog box, click To Node(s) and go to Step
(Figure
Cisco ONS 15454 DWDM Installation and Operations Guide, R4.7
7-20
Up to 10 profiles, including the two reserved profiles, Inherited and Default, can be stored in
CTC.
7-26.)
a
and
b
for each severity you want to customize. Refer to the following guidelines
All Critical (CR) or Major (MJ) default or user-defined severity settings are demoted to
Minor (MN) in Non-Service-Affecting (NSA) situations as defined in Telcordia GR-474.
Default severities are used for all alarms and conditions until you create and apply a new profile.
Changing a severity to inherited (I) or unset (U) does not change the severity of the alarm.
7-9).
Step
10) is created. This profile duplicates the default profile severities
"DLP-G124 Apply Alarm Profiles to Cards and Nodes"
Chapter 7
Manage Alarms