4 Faults and alarms
4.2 List of faults and alarms
Remedy:
The index of the encoder data set associated with the drive data set should be entered into p0187 (1st encoder),
p0188 (2nd encoder) and p0189 (3rd encoder).
F07503
EPOS: STOP cam approached with the incorrect traversing direction
Message value:
%1
Message class:
Application / technological function faulted (17)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The STOP cam MINUS was approached in the positive traversing direction or the STOP cam PLUS was approached
in the negative traversing direction.
Remedy:
- check the wiring of the STOP cam (BI: p2569, BI: p2570).
- check the traversing direction to approach the STOP cam.
A07504
Drive: Motor data set is not assigned to a drive data set
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, ENC, VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
A motor data set is not assigned to a drive object.
All of the existing motor data sets in the drive data sets must be assigned using the MDS number (p0186[0...n]).
There must be at least as many drive data sets as motor data sets.
Alarm value (r2124, interpret decimal):
Number of the motor data set that has not been assigned.
Remedy:
In the drive data sets, assign the non-assigned motor data set using the MDS number (p0186[0...n]).
- check whether all of the motor data sets are assigned to drive data sets.
- if required, delete superfluous motor data sets.
- if required, set up new drive data sets and assign to the corresponding motor data sets.
See also: p0186 (Motor Data Sets (MDS) number)
A07505
EPOS: Task fixed stop not possible in the U/f/SLVC mode
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
VECTOR_G
Reaction:
NONE
Acknowledge:
NONE
Cause:
In the U/f/SLVC mode, an attempt was made to execute a traversing block with the "fixed stop" task. This is not
possible.
Alarm value (r2124, interpret decimal):
Number of the traversing block with an illegal task parameter.
Remedy:
- Check the traversing block and change the task.
- change the open-loop/closed-loop control mode (p1300).
See also: p1300 (Open-loop/closed-loop control operating mode)
F07509
Drive: Component assignment missing
Message value:
%1
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Drive object:
B_INF, ENC, VECTOR_G
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A Drive Data Set (DDS) is assigned to a Motor Data Set (MDS) or Encoder Data Set (EDS) that does not have a
component number.
1462