Open-Loop/Closed-Loop Control Operating Mode; U/F Control Configuration / U/F Config - Siemens SINAMICS G120X Operating Instructions Manual

Infrastructure converter for hvac/water/wastewater
Hide thumbs Also See for SINAMICS G120X:
Table of Contents

Advertisement

Parameters
7.2 Parameter list
4:
7:
20:
Dependency:
For Standard Drive Control (p0096 = 1), settings p1300 = 0, 2 are possible, for Dynamic Drive Control (p0096 = 2) only
p1300 = 20 can be set.
Only operation with U/f characteristic is possible if the rated motor speed is not entered (p0311).
See also: p0300, p0311, p0500
NOTICE
Active slip compensation is required in the U/f control types with Eco mode (p1300 = 4, 7). The scaling of the slip
compensation (p1335) should be set so that the slip is completely compensated (generally 100%).
The Eco mode is only effective in steady-state operation and when the ramp-function generator is not bypassed. In
the case of analog setpoints, if required the tolerance for ramp-up and ramp-down should be actively increased for the
ramp-function generator using p1148 in order to reliably signal a steady-state condition.
Note
For motors, type p0300 = 6 and 6xx, operation with U/f control is only recommended for diagnostic purposes.
p1300[0...n]
Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode
G120X_DP (PM330),
Access level: 2
G120X_PN (PM330),
Can be changed: C2(1), T
G120X_USS (PM330)
Unit group: -
Min:
0
Description:
Sets the open and closed-loop control mode of a drive.
Value:
0:
1:
2:
4:
7:
20:
Dependency:
For Dynamic Drive Control (p0096 = 2), only p1300 = 20 can be set.
Only operation with U/f characteristic is possible if the rated motor speed is not entered (p0311).
See also: p0300, p0311, p0500
NOTICE
Active slip compensation is required in the U/f control types with Eco mode (p1300 = 4, 7). The scaling of the slip
compensation (p1335) should be set so that the slip is completely compensated (generally 100%).
The Eco mode is only effective in steady-state operation and when the ramp-function generator is not bypassed. In
the case of analog setpoints, if required the tolerance for ramp-up and ramp-down should be actively increased for the
ramp-function generator using p1148 in order to reliably signal a steady-state condition.
Note
For motors, type p0300 = 14, operation with U/f control is only recommended for diagnostic purposes.
p1302[0...n]

U/f control configuration / U/f config

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the configuration for the U/f control.
Bit field:
Bit
668
U/f control with linear characteristic and ECO
U/f control for a parabolic characteristic and ECO
Speed control (encoderless)
U/f control with linear characteristic
U/f control with linear characteristic and FCC
U/f control with parabolic characteristic
U/f control with linear characteristic and ECO
U/f control for a parabolic characteristic and ECO
Speed control (encoderless)
Signal name
Calculated: -
Scaling: -
Unit selection: -
Max:
20
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Data type: Integer16
Dynamic index: DDS, p0180
Function diagram: 6300, 6301,
6851, 8012
Factory setting:
20
Data type: Unsigned16
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
0000 0000 0000 0000 bin
0 signal
FP
SINAMICS G120X converter