Flying restart operating mode / FlyRest op_mode

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets the operating mode for flying restart.
The flying restart allows the drive converter to be switched on while the motor is still rotating. In so doing, the drive
converter output frequency is changed until the actual motor speed/velocity is found. The motor then accelerates up
to the setpoint at the ramp-function generator setting.
Value:
0:
1:
4:
Dependency:
A differentiation is made between flying restart for U/f control and for vector control (p1300).
Flying restart, U/f control: p1202, p1203, r1204
Flying restart, vector control: p1202, p1203, r1205
For synchronous motors, flying restart cannot be activated.
See also: p1201
See also: F07330, F07331
NOTICE
The "flying restart" function must be used in cases where the motor may still be running (e.g. after a brief line supply
interruption) or is being driven by the load. The system might otherwise shut down as a result of overcurrent.
Note
For p1200 = 1, 4, the following applies:
Flying restart is active after faults, OFF1, OFF2, OFF3.
For p1200 = 1, the following applies:
The search is made in both directions.
For p1200 = 4, the following applies:
The search is only made in the setpoint direction.
For U/f control (p1300 < 20), the following applies:
The speed can only be sensed for values above approx. 5 % of the rated motor speed. For lower speeds, it is assumed
that the motor is at a standstill.
If p1200 is changed during commissioning (p0010 > 0), then it is possible that the old value will no longer be able to be
set. The reason for this is that the dynamic limits of p1200 have been changed by a parameter that was set when the
drive was commissioned (e.g. p0300).
p1201[0...n]

BI: Flying restart enable signal source / Fly_res enab S_src

Access level: 3
Can be changed: T
Unit group: -
Min:
-
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Fixed setpoint bit 2
Fixed setpoint bit 3
Inhibit negative direction
Inhibit positive direction
Setpoint inversion
Motorized potentiometer raise
Motorized potentiometer lower
Bypass ramp-function generator
Flying restart inactive
Flying restart always active (start in setpoint direction)
Flying restart always active (start only in setpoint direction)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
4
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Parameters
7.3 Parameters
No
3010
No
3010
No
3040
No
3040
No
3040
No
3020
No
3020
No
3070
Data type: Integer16
Dynamic index: DDS, p0180
Function diagram: 6300, 6850
Factory setting:
0
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: -
Factory setting:
1