Fip-Snooping Enable; Fip-Snooping Fc-Map - NETGEAR M6100 Series Reference Manual

Hide thumbs Also See for M6100 Series:
Table of Contents

Advertisement

fip-snooping enable

Use the fip-snooping enable command in VLAN Configuration mode to enable
snooping of FIP packets on the configured VLANs. FIP snooping is disabled on VLANs by
default.
Priority Flow Control (PFC) must be operationally enabled before FIP snooping can operate
on an interface. VLAN tagging must be enabled on the interface in order to carry the dot1p
value through the network.
This command can only be entered after FIP snooping is enabled using the
priority-flow-control mode
Default
disabled
Format
feature fip-snooping
Mode
VLAN Config
Command example:
The following example enables FIP snooping on VLANs 2 through 8:
s1(config)#vlan 2-8
s1(config-vlan)#fip-snooping enable
no fip-snooping enable
Use this command to return the mode to the default (off).
Format
no feature fip-snooping
Mode
VLAN Config
Command example:
The following example disables FIP snooping on VLANs 2 through 8.
s1(config)#vlan 2-8
s1(config)(vlan 2-8)#no fip-snooping enable
s1(config)(vlan 2-8)# exit

fip-snooping fc-map

Use the fip-snooping fc-map command in VLAN Configuration mode to configure the
FP-MAP value on a VLAN. The FC map value is used to help in securing the switch against
misconfiguration.
When configured using fabric-provided MAC addresses, FCoE devices transmit frames
containing the FC map value in the upper 24 bits. Only frames that match the configured FC
map value are passed across the VLAN. Frames with MAC addresses that do not match the
FC map value are discarded.
M6100 Series Switches
command. Otherwise, it does not appear in the CLI syntax tree.
Data Center Commands
599